Full-scale
shake table testing
A full-scale portion of a DIS
Floor Isolation System, comprising
two modules connected by stringers,
was shake table tested at the
University of Nevada, Reno.
More than 100
earthquake tests, including
75 DBE (Design Basis Earthquakes)
and MCE (Maximum Credible Earthquake)
motions were performed.
This suite
of tests was extreme with maximum
accelerations of 6g and floor
displacements relative to the
shake table of 18 inches. The
results showed good agreement
with the performance predicted
by nonlinear computer models.
Peak Accelerations and spectral
accelerations were reduced by
up to a factor of 7.
|